2024, Number 3
<< Back Next >>
Rev Mex Pediatr 2024; 91 (3)
Acoustic and lighting assessment in neonatal hospital areas in an obstetrics and gynecology hospital
Vásquez-Sotelo DS, Pérez-Miguel OA
Language: Spanish
References: 15
Page: 88-91
PDF size: 281.27 Kb.
ABSTRACT
Introduction: in neonatal hospital units it is important to analyze exposure to decibels (dB) and lux, especially premature infants, who, due to their anatomical and functional immaturity, may have their ability to adapt to the extrauterine environment compromised.
Objective: to measure the levels of acoustic and light stimulation in hospital areas where newborns are cared for.
Material and methods: the evaluation was carried out in four hospitalization areas, measuring noise levels in dB (sound meter version 2.2, with maximum noise level 120 dB) and luxes (Smart tools luxometer), for 48 days.
Results: the acoustic and light stimulation levels were above the recommended limits to avoid hearing and visual damage.
Conclusions: auditory and light stimulation was found to be above the recommended safe limits. Controlling luxes and decibels can help reduce their harmful effects.
REFERENCES
Graven SN, Browne JV. Auditory development in the fetus and infant. Newborn Infant Nurs Rev. 2008; 8(4): 187-193.
Cabezas CM. La importancia del entorno en los recién nacidos prematuros durante el ingreso hospitalario. Ágora de Enfermería. 2010; 14(1): 9-16.
Almadhoob A, Ohlsson A. Sound reduction management in the neonatal intensive care unit for preterm or very low birth weight infants. Cochrane Database Syst Rev. 2020; 1(1): CD010333. doi: 10.1002/14651858.CD010333.pub3.
Quiñones C, Menéndez D, Cruz V, Hernández B, Dávila A. Retinopatía del prematuro. Rev Cubana Pediatr. 2015; 87(1): 69-81.
Jordao KR, Pinto LA, Machado LR, Costa LB, Trajano ET. Possible stressors in a neonatal intensive care unit at a university hospital. Rev Bras Ter Intensiva. 2016; 28(3): 310-314. doi: 10.5935/0103-507X.20160041.
Lai TT, Bearer CF. Iatrogenic environmental hazards in the neonatal intensive care unit. Clin Perinatol. 2008; 35(1): 163-181. doi: 10.1016/j.clp.2007.11.003.
Rodrígueza RG, Pattini A. Iluminación en unidades de cuidados intensivos neonatales: actualización y recomendaciones. Arch Argent Pediatr. 2016; 114(4): 361-367.
Secretaría de Gobernación. Norma Oficial Mexicana PROY-NOM-025-SSA3-2011, Para la organización y funcionamiento de las unidades de cuidados intensivos. Diario Oficial de la Federación [Internet]. México: 2012. Recuperado de: https://www.dof.gob.mx/nota_detalle.php?codigo=5234984&fecha=23/02/2012#gsc.tab=0
Gallegos-Martínez J, Reyes-Hernández J, Fernández Hernández VA, González-González LO. Índice de ruido en la unidad neonatal. Su impacto en recién nacidos. Acta Pediatr Mex. 2011; 32(1): 5-14.
Rodríguez-Balderrama, Sámano-Muciño C, Cisneros-Hernández J, Nieto Sanjuanero A, Ochoa-Correa E, Cárdenas-del Castillo B, De la O-Cavazos M. Hablar al lado del paciente aumenta los decibeles en la UCIN de un hospital de tercer nivel. Perinatol Reprod Hum. 2022; 36(2): 46-50. doi: 10.24875/per.22000008.
Vargas Chávez DA, Luna MM, Braverman Bronstein A, Iglesias Leboreiro J, Bernárdez Zapata I. Medición y análisis de los niveles de ruido en una unidad de cuidados intensivos neonatales. An Med (Mex). 2018; 63(3): 165-168.
Miquel Capó RN. Intervenciones enfermeras sobre el ambiente físico de las Unidades de Cuidados Intensivos Neonatales. Enferm Intensiva. 2016; 27(3): 96-111. doi: 10.1016/j.enfi.2016.01.002.
Chafloque A, Aspajo E. Relación entre el nivel de luminosidad en una unidad de cuidado intensivo neonatal y la retinopatía de la prematuridad Lima Perú-2018. Rev Peru Investig Matern Perinat. 2019; 8(4): 9-13. Disponible en: https://doi.org/10.33421/inmp.2019167
Oliveira F, Paiva M, Nascimento M, Rezende V, Silva A, Silva C. Nível de ruído da unidade de terapia intensiva pediátrica: estudo observacional correlacional. Online Braz J Nurs. 2013; 12: 431-441. Available in: http://www.objnursing.uff.br/index.php/nursing/article/view/4043
Almadhoob A, Ohlsson A. Sound reduction management in the neonatal intensive care unit for preterm or very low birth weight infants. Cochrane Database Syst Rev. 2015; 1: CD010333. doi: 10.1002/14651858.CD010333.pub2.